2. INSTALLATION
2. Pre-Installation, continued
Hardware / Materials Required
Conduit, strain - reliefs and appropriate fittings
1/4" mounting bolts and lock washers Electrical tape
Wire ties
Tools Required
Misc screw drivers Level 1/2" wrench
Drill and drill bits Pliers Wire strippers
Level Pencil or Marker Multimeter
Wiring
Pre-plan the wire and conduit runs. For maximum safety, run both AC and DC wires/cabling in
(separate) conduit. Direct current wiring, due to its potential to generate RFI, should
be tied together with electrical tape. Wiring and installation methods must conform
to all applicable electrical codes.
NOTE: Run DC cabling in twisted pairs, keeping the runs as short as practical.
AC Connections
Use #10 AWG (or larger) THHN wire for all AC wiring. The inverter’s AC terminal
blocks accept up to #6 AWG wire.
DC Connections
Battery to inverter cabling should be only as long as required. If using #2/0 AWG
cables, do not exceed 5 feet (one way) for 12 VDC systems.
Crimped and sealed copper ring terminal lugs with a 5/16” hole should be used to connect the
battery cables to the inverter’s DC terminals.
AC Grounding
The ME Series inverter/charger contains an internal neutral-to-ground switching
circuit for the AC electrical system.
WARNING: The AC shore power neutral must be grounded ONLY through the shore power cable. Do not
ground AC to the vehicle’s chassis.
DC Grounding
The inverter/charger should always be connected to a permanent, grounded wiring system. For the
majority of installations, the negative battery conductor is bonded to the vehicle’s
safety-grounding conductor (green wire) at only one point in the system. The size for the
conductor is usually based on the size of the largest conductor in the DC system. DO NOT connect the
battery negative (- ) cable to the vehicle’s safety ground. Connect it only to the inverter’s
negative battery terminal. If there are any non-factory installed DC appliances on board
the vehicle, DO NOT ground them at the safety ground. Ground them only at the negative bus of the
DC load center (as applicable).