3. Operation, continued
Float –
At the end of absorption time, the charger reduces the
charge voltage to the float voltage setting for the battery
type selected. See Chart 1.
Battery Saver
TM
-
Battery saver mode is a new and unique setting to Magnum
Energy’s inverter/chargers. It maintains the batteries
without “overcharging” thus preventing excessive loss of
water in flooded batteries or drying out of AGM batteries.
When the charger enters battery saver mode, it turns off
and monitors the battery voltage if there is no float charge
current to the batteries after 4 hours. When the battery
voltage drops to 12.9 VDC, the charger turns on and float
charges the batteries to a nominal level. Once that level
has been reached, the charger returns to battery saver
mode to monitor the batteries.
Equalize –
The battery charger is delivering equalize voltage to the
batteries for a maximum of 4 hours. See Chart 1. Press
and hold the switch down for 5 seconds to initiate EQ. The
LED will blink fast.
NOTE: Equalize mode will not start until the charger is in
float or battery saver mode.