2004 - Magnum Energy, Inc.
Weight (Controller) 1 lb (0.5 kg)
Weight (Switch) 0.25 lb (0.1 kg)
Dimensions (Controller) 3.0 H x 5.2 W x 1.33 D
(7.6 cm H x 13.2 cm W x 3.3 cm D)
Dimensions (Switch) 2.25 H x 3.25 W x 1.5 D
(5.7 cm H x 8.3 cm W x 3.8 cm D)
Electrical Requirements 12 VDC or 24 VDC
Controls Enable, Off, Test
LED Indicator On, Off, Fault Condition
Temp Sense Range 65 °F to 85 °F (18 °C to 29 °C)
75 °F (25 °C) - factory setting
Voltage Start Range 10 VDC to 12 VDC (or)
20 VDC to 24 VDC
Quiet Time Range 9PM to 7AM, 9PM to 8AM, 9PM to 9AM,
10PM to 8AM, 11PM to 8AM
Clock 24 hour
Generator Run Range 1 to 5 hours
2 hours - factory setting
Connections Screw Terminals (rear mounted)
Electrical Connections Gen B+ (from Gen Hour Meter) +12 VDC
+12 VDC or +24 VDC Pos (from Battery)
-12 VDC or -24 VDC Neg (from Battery)
Generator Start
Common (from Gen Start/Stop Switch)
Generator Stop/Preheat
14
Specifications at 25 °C
Subject to change without notice
5. Specifications
Table 2 - AGS Menu Tree
AutoGenSt Cntrl
AutoGenSt OFF
AutoGenSt Enabl
AutoGenSt Test
AGS w/Quiet Time
Set Current Time
Set Hour 12:00A
Set Minutes 12:00A
Set AM/PM 12:00A
AGS