LED INDICATION SYMPTOM OPERATION/SOLUTION
RED Gen won't start. Check Gen start wiring,
= GEN FAULT Turn "off" then "enable"
to reset.
RED Gen won't stay Check Gen B+ wiring,
= GEN FAULT on. check gen, turn "off"
then "enable" to reset.
GREEN BLINK Gen start initiated. No problem.
= GEN START
GREEN SOLID Gen started ok. No problem.
= GEN START
READY OFF No 12 or 24 volt Check fuse, check
= POWER OFF DC power to control 12 or 24 volt DC wiring,
box. Turn "off" then "enable"
to reset.
READY BLINK No remote control Check remote
= NO REMOTE sensed or plugged connections,
in. Turn "off" then "enable"
to reset.
READY SOLID Normal operation. No problem.
= POWER ON
15
To test the system for proper operation, hold the AGS Switch in
the "TEST" position and release. The generator should start and
run for 30 seconds and then shut off. If the generator does not
start and stop as expected, refer to the troubleshooting chart
below. If the problem persists, contact your dealer.