2. Configuration
Table 1 - Magnum AGS Software Revs (4/2/04)
VERSION V 2.0 V 2.1
DATE March 1, 2004 March 1, 2004
START TYPE 3-wire start 3-wire start
GEN TYPES Onan Quiet Diesel Most gas and other diesels:
Emerald, Marquis, MicroLite,
MicroQuiet, Onan, and PowerTech
FEATURES Temp & low voltage start Temp & low voltage start
Quiet time, & net enabled Quiet time & net enabled
12 or 24 volt DC operation 12 or 24 volt DC operation
(jumper select) (jumper select)
Software version Software version
(jumper select) (jumper select)
Temp start (connects 3 ways) Temp start (connects 3 ways)
Directly to a/c thermostat Directly to a/c thermostat
Uses a sensor only Uses a sensor only
Wall switch Wall switch
(stand alone operation only) (stand alone operation only)
NETWORK Connects to ME inverter Connects to ME inverter
PORT (uses ME-RC remote with (uses ME-RC remote with
version 0.5 or higher) version 0.5 or higher)
REMOTE Stand alone switch, Stand alone switch,
PORT pigtail direct to a/c thermostat, pigtail direct to a/c thermostat,
or sensor only or sensor only
START RELAY closes for 20 seconds closes for 10 seconds
(pin 5&6)
STOP RELAY closes for 10 seconds closes for 10 seconds
(pin 6&7)
AUX RELAY N/A N/A
(pin 1&8)
RELAY SEQ Stop 10 sec, Delay 4 sec, Stop 10 sec, Delay 4 sec,
Start 20 sec Start 10 sec
B+ Voltage 10 VDC 10 VDC
(min at pin 2)
B+ GEN RUN checks for B+ 2 sec checks for B+ 2 sec
(pin 2) after crank time after crank time
TEST MODE Ignores B+ for test Ignores B+ for test
(runs 30 sec then off) (runs 30 sec then off)
GEN START Yes, ignores auto start Yes, ignores auto start
(MANUAL) (if B+ present) (if B+ present)
Allows manual start Allows manual start
within quiet time within quiet time
LED, GREEN Blinks on start, solid on run Blinks on start, solid on run
LED, RED Red after 4 tries Red after 4 tries
(Time between tries = 2 min) (Time between tries = 2 min)